The Apatlas 3 Phase UPS System provides power protection for small – medium server rooms, data Centres, industrial, telecom and other mission critical applications.
The Apatlas UPS range is from 10kVA up to 300kVA and can be parallel up to 2MVA.
- True online double conversion technology
- IGBT PWM Rectifier and inverter technology
- Multi-micro processor controller
- Low input current THD (<3%)
- High input power factor 0.99
- High efficiency typically 93% – 95%
- Dual mains input
- 500 Event log with detailed records
- Multi lingual function
- Auto restart function
- Cold start function
- Emergency power off
- Customisable as a frequency converter
- Overload and short circuit protection
- Static and manual bypass operation
MODEL | 3310 | 3315 | 3320 | 3330 | 3340 | 3360 | 3380 | 33100 | 33150 | 33200 |
Capacity VA | 10kVA | 15KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA | 100KVA | 150KVA | 200KVA |
Power W | 8kW | 12kW | 16kW | 24kW | 32kW | 48kW | 64kW | 80kW | 120kW | 160kW |
Output pF | 0.8pF |
Input | |
Input Voltage Range | 140-280 VAC (L-N) 3phase+N |
Input Power Factor | >0.99 |
Input Frequency Range | 50Hz ± 10% /60Hz ± 10% (Selectable) |
Total Harmonic Distortion |
(THDI) with linear load <3% |
OUTPUT | |
Output Voltage Range |
220/380 VAC, 230/400 VAC, 240/415 VAC 3 phase + N ± 1% |
Recovery Time | ± 1 static, +3 dynamic at 100% load, 5ms |
Efficiency | Normal mode up to 94%. Eco Mode 98% |
Output Frequency Range | 50Hz / 60Hz ± 0.01% (Battery mode) |
Output THD | Linear load < 2% / Non linear load <3% |
Crest Factor | 3:1 |
Overload Capacity | 110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute |
Short Circuit Protection | IGBT Controlled electronic short protection |
BATTERY | |
Type | Sealed lead acid maintenance free |
Quantity | Selectable depending on kVA. (From 28 to 50) |
Battery Test | Programmable without load, autonomy battery test |
Battery Temperature | 20C – 25C (for maximum efficiency) |
BYPASS | |
Input Voltage Range | 380/400/415 3 phase + N ± 10% selectable |
Transfer Time | <1 ms |
COMMUNICATION | |
Communication Ports | RS232 / RS485 / RJ11 / SNMP |
Dry Contact Alarms | Optional card (7 dry contacts alarms) |
Software | UPSnet software, Megatech, SES, compatibility with all protocols |
SNMP Card | Optional |
Advanced Communications | MOD-Bus, J-BUS/Profibus/Model/Web/Telnet/GPRS/CAN-Bus, SNMP |
CERTIFICATION | |
Quality | ISO 9001 : 2008, ISO 14001 |
Standard | CE |
Safety | EN62040-1-1, IEC60950 |
EMC/LCD | 50091-2, Class A |
GENERAL | |
Technology | Online double conversion, tranformerless, DSP + FPGI Full digital control. SWPM Controlled, SMD Technology main board (all in one). 1/1,3/1, 1/3,3/3 Factory set for input output customisable as a frequency converter |
Design | Superior design that enables fast maintenance and serviceability |
Front Panel | 20mm, LCD front panel + mimic diagram |